OPC UA via Telegraf

Collect OPC UA tags with Telegraf into an Arc Enterprise cluster: writer endpoint behind a load balancer, RBAC-scoped write tokens per collector, plus security, node IDs and quality codes.

Arc has no native OPC UA client. Telegraf has two OPC UA input plugins and a native Arc output plugin, so Telegraf is the bridge: it runs next to the OPC UA server, reads tags over an encrypted session, and writes them to Arc in MessagePack columnar batches.

Versions

outputs.arc needs Telegraf 1.37 or later. Use Telegraf 1.39.0 or later if you subscribe with inputs.opcua_listener and address nodes by namespace URI (namespace_uri or nsu=): earlier releases fail at startup with namespace urls require a server NamespaceArray (influxdata/telegraf#18681). Everything on this page was tested with Telegraf 1.40.2 and Arc 26.09.3 against the Microsoft OPC PLC simulator 2.12.48.

In a cluster

Point outputs.arc at the writer endpoint (behind an L7 load balancer if you run more than one writer), and point dashboards at a reader endpoint. Give each collector its own token, scoped with RBAC to the databases it writes. Everything else on this page is the same as on Arc OSS.

Polling or subscriptions

inputs.opcuainputs.opcua_listener
How it readsReads every node on each Telegraf intervalSubscribes; the server sends a notification when a value changes
Rows writtenOne per node per interval, changed or notOne per change, filtered by trigger and deadband
Recommended timestampgathersource
Good forDashboards on a regular time grid, data-quality reporting with a known expected countSetpoints, states and alarms that change rarely, exact time of change, constrained networks

Both can run against the same server at the same time. Writing them to separate Arc databases keeps the regular samples and the change events apart.

Prerequisites

  • Telegraf, at the version in the callout above
  • An Arc Enterprise writer endpoint (or the load balancer in front of the writers) reachable from the Telegraf host
  • arcli, connected to Arc with an admin token
  • An OPC UA endpoint URL, a user Telegraf can log in as, and the node IDs you want to read
  • Network access from Telegraf to the OPC UA server port (often 4840; 50000 in the examples)

Quick start

1. Create a write-only token

Telegraf only needs to write. With arcli connected as an admin (see First connection), create a token that cannot read or delete, against any node of the cluster (tokens replicate cluster-wide):

arcli auth token create --name telegraf-plant-a --permission write \
  --description "OPC UA collector, plant A"

arcli prints the secret on stdout, once, and this on stderr:

Created token "telegraf-plant-a" (id 2). Store the secret securely; it cannot be retrieved again.

Check what the new token can do. Pass it with flags: arcli also reads an ARC_TOKEN environment variable, and --token needs --endpoint.

arcli ping --endpoint http://<arc-node>:8000 --token "<token>"
arcli query --endpoint http://<arc-node>:8000 --token "<token>" "SHOW DATABASES"
endpoint:   http://<arc-node>:8000 (connection (flags))
health:     ok (uptime 16.102434632s, latency 2.2ms) storage: hot=ok
auth:       ok as "telegraf-plant-a" (id 2, write) — not admin; `auth token` commands will be refused
Error: arc: Permission denied: read required (HTTP 403)

On its own, this token can write to every database. To limit it to plant and plant_events, add it to a team whose role grants write on those databases, as described in RBAC. Once a token has a team membership, its role permissions apply instead of the token's own --permission list.

2. Configure Telegraf

This polls four tags from a boiler and two test signals once per second over a Basic256Sha256 / SignAndEncrypt session with username authentication. BadFastUInt1 is a simulator node that deliberately returns bad and uncertain status codes; it feeds the quality example below.

[agent]
  interval = "1s"
  flush_interval = "5s"
  omit_hostname = true

[[inputs.opcua]]
  endpoint = "opc.tcp://opc-plc:50000"

  security_policy = "Basic256Sha256"
  security_mode = "SignAndEncrypt"

  ## Persist the client certificate so the server only has to trust it once.
  certificate = "/var/lib/telegraf/telegraf-cert.pem"
  private_key = "/var/lib/telegraf/telegraf-key.pem"

  auth_method = "UserName"
  username = "telegraf"
  password = "${OPCUA_PASSWORD}"

  timestamp = "gather"

  ## Keep "uncertain, last usable value" readings instead of dropping them.
  [inputs.opcua.workarounds]
    additional_valid_status_codes = ["0x40900000"]

  [[inputs.opcua.group]]
    name = "boiler"
    namespace_uri = "http://microsoft.com/Opc/OpcPlc/Boiler"
    identifier_type = "i"
    default_tags = { site = "plant-a", asset = "boiler-2" }
    nodes = [
      {name = "current_temperature", identifier = "6211"},
      {name = "target_temperature",  identifier = "6217"},
      {name = "heater_on",           identifier = "6212"},
      {name = "overheated",          identifier = "6214"},
    ]

  [[inputs.opcua.group]]
    name = "line_signals"
    namespace_uri = "http://microsoft.com/Opc/OpcPlc/"
    identifier_type = "s"
    default_tags = { site = "plant-a", asset = "line-1" }
    nodes = [
      {name = "spike_data",      identifier = "SpikeData"},
      {name = "bad_fast_uint_1", identifier = "BadFastUInt1"},
    ]

## "The operation succeeded. StatusGood (0x0)" -> quality = "0x0"
[[processors.regex]]
  order = 1
  [[processors.regex.fields]]
    key = "Quality"
    pattern = '^.*\((0x[0-9A-Fa-f]+)\)$'
    replacement = "${1}"

[[processors.rename]]
  order = 2
  [[processors.rename.replace]]
    field = "Quality"
    dest = "quality"

[[outputs.arc]]
  url = "http://<writer-endpoint>:8000/api/v1/write/msgpack"
  api_key = "${ARC_TOKEN}"
  database = "plant"
  content_encoding = "gzip"

ARC_TOKEN is the write-only token from step 1 and OPCUA_PASSWORD is the OPC UA user's password, both read from Telegraf's environment.

3. Test, then run

Print what Telegraf reads without writing anything:

telegraf --config telegraf.conf --test
> boiler,asset=boiler-2,id=nsu\=http://microsoft.com/Opc/OpcPlc/Boiler;i\=6211,site=plant-a current_temperature=71,quality="0x0" 1793109791000000000
> boiler,asset=boiler-2,id=nsu\=http://microsoft.com/Opc/OpcPlc/Boiler;i\=6217,site=plant-a quality="0x0",target_temperature=80 1793109791000000000

Then start Telegraf normally.

4. Query the data

SELECT time, asset, id, current_temperature, target_temperature, heater_on, overheated, quality
FROM plant.boiler
ORDER BY time DESC
LIMIT 4;
time                 | asset    | id                                                | current_temperature | target_temperature | heater_on | overheated | quality
---------------------+----------+---------------------------------------------------+---------------------+--------------------+-----------+------------+--------
2026-10-27T14:19:13Z | boiler-2 | nsu=http://microsoft.com/Opc/OpcPlc/Boiler;i=6211 | 18                  | NULL               | NULL      | NULL       | 0x0
2026-10-27T14:19:13Z | boiler-2 | nsu=http://microsoft.com/Opc/OpcPlc/Boiler;i=6217 | NULL                | 80                 | NULL      | NULL       | 0x0
2026-10-27T14:19:13Z | boiler-2 | nsu=http://microsoft.com/Opc/OpcPlc/Boiler;i=6212 | NULL                | NULL               | true      | NULL       | 0x0
2026-10-27T14:19:13Z | boiler-2 | nsu=http://microsoft.com/Opc/OpcPlc/Boiler;i=6214 | NULL                | NULL               | NULL      | false      | 0x0

Each node is its own row. See Mapping nodes to measurements for why, and how to query it.

Connection and security

Endpoint

endpoint is the server's opc.tcp://host:port URL. An OPC UA client first asks the server for its endpoint descriptions, then connects to the URL the server advertises. If the server advertises a hostname that Telegraf cannot resolve (a container ID, a PLC's internal name), the connection fails after the first request succeeds. Configure the server to advertise a resolvable hostname, or make the name resolvable from the Telegraf host.

Security policy and mode

OptionValuesDefault
security_policyNone, Basic128Rsa15, Basic256, Basic256Sha256, autoauto
security_modeNone, Sign, SignAndEncrypt, autoauto

Set both explicitly in production so a misconfigured server cannot negotiate the session down. Basic256Sha256 with SignAndEncrypt is the strongest combination the plugin offers. If no endpoint on the server matches the configured policy and mode, Telegraf fails before connecting:

E! [inputs.opcua] Error in plugin: connect failed: security policy "http://opcfoundation.org/UA/SecurityPolicy#None": no suitable endpoint found: no suitable server endpoint found

Client certificate

With certificate and private_key unset, Telegraf creates a temporary self-signed certificate on every start. If you set both paths and the files do not exist, Telegraf creates a self-signed certificate there and keeps it. Use persistent paths: the server has to trust the client certificate, and a new certificate on every restart means trusting it again every time.

The usual trust flow on a server that does not auto-accept clients:

  1. Start Telegraf once. The connection is refused, and most servers store the untrusted client certificate in a rejected list.
  2. Move that certificate to the server's trusted list (the exact step depends on the server or PLC vendor).
  3. Restart Telegraf.

remote_certificate points Telegraf at an additional, explicitly trusted certificate for the server.

The official telegraf container image drops privileges to the telegraf user, which can write to /var/lib/telegraf. Mount a named volume there for the certificate. A bind-mounted host directory is often not writable by that user.

Authentication

auth_method is Anonymous (default), UserName or Certificate. With UserName, set username and password, and keep the password out of the file by referencing an environment variable as above. Give Telegraf its own OPC UA user with read access to the nodes it needs.

Node IDs

A node ID has a namespace and an identifier. Telegraf accepts four equivalent forms, all tested against the same node:

nodes = [
  {name = "by_id_uri",   id = "nsu=http://microsoft.com/Opc/OpcPlc/Boiler;i=6211"},
  {name = "by_id_index", id = "ns=4;i=6211"},
  {name = "by_index",    namespace = "4", identifier_type = "i", identifier = "6211"},
  {name = "by_uri",      namespace_uri = "http://microsoft.com/Opc/OpcPlc/Boiler", identifier_type = "i", identifier = "6211"},
]

identifier_type is i (numeric), s (string), g (GUID) or b (opaque). Use either id or the namespace/namespace_uri + identifier_type + identifier combination, not both.

Prefer namespace_uri (or nsu= in id). A namespace index (ns=4) is a position in the server's namespace array, and the server assigns it. Loading other companion models, upgrading firmware or pointing the same config at a second server can change it, and the config then reads the wrong node or fails with StatusBadNodeIDUnknown. A namespace URI is stable; Telegraf resolves the index when it connects. Telegraf's log lines show the resolved form, for example ns=3;s=BadFastUInt1.

A group can set namespace_uri and identifier_type once for all its nodes, as in the quick start.

Mapping nodes to measurements

Groups, tags and fields

  • Each [[inputs.opcua.group]] name becomes an Arc measurement (a table). Without groups, the plugin-level name is used (default opcua for inputs.opcua, opcua_listener for inputs.opcua_listener).
  • default_tags become tag columns on every row of the group.
  • Each node's name becomes a field column.
  • optional_fields = ["DataType"] on the input adds each node's OPC UA data type as a DataType field.

Model one measurement per asset class, with tags for site and asset and fields for values. Every boiler goes into boiler, told apart by asset, so a fleet-wide query is one GROUP BY rather than a UNION across tables.

One row per node

Telegraf emits every node as its own metric with an id tag holding the full node ID and its own Quality field, so Arc stores one row per node per read, with NULL in the other value columns. SQL aggregates skip NULL, so per-asset queries work directly:

SELECT
  date_trunc('minute', time)                  AS minute,
  ROUND(AVG(current_temperature), 1)          AS avg_temp,
  MAX(current_temperature)                    AS max_temp,
  MAX(target_temperature)                     AS target,
  ROUND(100 * AVG(heater_on::INT))            AS heater_on_pct,
  COUNT(*) FILTER (WHERE overheated)          AS overheated_s
FROM plant.boiler
WHERE asset = 'boiler-2'
  AND time > NOW() - INTERVAL '1 hour'
GROUP BY minute
ORDER BY minute;

With 1-second polling and gather timestamps, COUNT(*) FILTER (WHERE overheated) counts seconds.

You can fold a poll into one wide row by dropping the id tag and merging metrics that share a timestamp:

[[inputs.opcua]]
  ## ... connection settings and groups as above ...
  timestamp = "gather"
  tagexclude = ["id"]

[[aggregators.merge]]
  drop_original = true

drop_original = true matters: without it, both the narrow rows and the merged row reach Arc. One poll then becomes:

boiler,asset=boiler-2,site=plant-a current_temperature=69,heater_on=false,overheated=false,quality="0x0",target_temperature=80 1793110806000000000

This only works when every node in a read has the same timestamp (timestamp = "gather"), and the nodes' quality fields collide, so only one status code survives per row. Keep the narrow shape if per-node quality matters.

Quality and status codes

Every OPC UA value carries a status code: Good, Uncertain or Bad. Telegraf writes it to a Quality field as text, for example "The operation succeeded. StatusGood (0x0)". The processors.regex and processors.rename blocks in the quick start reduce it to the hex code in a quality field.

By default, Telegraf drops every reading whose status is not Good and logs an error instead:

E! [inputs.opcua] status not OK for node bad_fast_uint_1 (ns=3;s=BadFastUInt1): Whatever was updating this value has stopped doing so. StatusUncertainLastUsableValue (0x40900000)
E! [inputs.opcua] status not OK for node bad_fast_uint_1 (ns=3;s=BadFastUInt1): Data is missing due to collection started/stopped/lost. StatusBadDataLost (0x809D0000)

A dropped reading reaches Arc only as a missing row. To keep selected codes, list them in additional_valid_status_codes under [inputs.opcua.workarounds]. The quick start keeps 0x40900000 (Uncertain, last usable value) and still drops Bad codes.

With polling, the expected number of readings is known, so you can count both kinds of problem:

SELECT
  date_trunc('minute', time)                  AS minute,
  COUNT(*)                                    AS readings,
  COUNT(*) FILTER (WHERE quality = '0x0')     AS good,
  COUNT(*) FILTER (WHERE quality <> '0x0')    AS uncertain,
  60 - COUNT(*)                               AS dropped
FROM plant.line_signals
WHERE id = 'nsu=http://microsoft.com/Opc/OpcPlc/;s=BadFastUInt1'
  AND time >= TIMESTAMP '2026-10-27 14:11:00'
  AND time <  TIMESTAMP '2026-10-27 14:16:00'
GROUP BY minute
ORDER BY minute;
minute               | readings | good | uncertain | dropped
---------------------+----------+------+-----------+--------
2026-10-27T14:11:00Z | 48       | 36   | 12        | 12
2026-10-27T14:12:00Z | 48       | 36   | 12        | 12
2026-10-27T14:13:00Z | 48       | 36   | 12        | 12
2026-10-27T14:14:00Z | 48       | 36   | 12        | 12
2026-10-27T14:15:00Z | 48       | 36   | 12        | 12

60 - COUNT(*) assumes a 1-second interval and complete minutes, so keep the window on minute boundaries.

Timestamps

timestampRow time is
gather (default)When Telegraf read the value
serverThe server's timestamp for the value
sourceWhen the value last changed at the device

Do not combine polling with source. A value that has not changed keeps its source timestamp, so every poll writes the same value with the same timestamp again. In testing, a setpoint polled every second for 50 seconds produced 50 rows with one distinct timestamp. Use gather (or server) for polling, and source for subscriptions.

Subscriptions with opcua_listener

inputs.opcua_listener shares the connection, security, authentication, timestamp and node options with inputs.opcua, but not the read-retry options. It adds subscription_interval, connect_fail_behavior, per-node monitoring parameters and event subscriptions; run telegraf --usage opcua_listener for the full list. The processors and outputs.arc blocks below are the same as in the quick start, except for database:

[agent]
  flush_interval = "5s"
  omit_hostname = true

[[inputs.opcua_listener]]
  endpoint = "opc.tcp://opc-plc:50000"
  subscription_interval = "1s"

  security_policy = "Basic256Sha256"
  security_mode = "SignAndEncrypt"
  certificate = "/var/lib/telegraf/telegraf-cert.pem"
  private_key = "/var/lib/telegraf/telegraf-key.pem"

  auth_method = "UserName"
  username = "telegraf"
  password = "${OPCUA_PASSWORD}"

  timestamp = "source"

  [[inputs.opcua_listener.group]]
    name = "boiler"
    namespace_uri = "http://microsoft.com/Opc/OpcPlc/Boiler"
    identifier_type = "i"
    default_tags = { site = "plant-a", asset = "boiler-2" }

    [[inputs.opcua_listener.group.nodes]]
      name = "current_temperature"
      identifier = "6211"
      [inputs.opcua_listener.group.nodes.monitoring_params]
        sampling_interval = "1s"
        queue_size = 10
        discard_oldest = true
        [inputs.opcua_listener.group.nodes.monitoring_params.data_change_filter]
          trigger = "StatusValue"
          deadband_type = "Absolute"
          deadband_value = 2.0

    [[inputs.opcua_listener.group.nodes]]
      name = "target_temperature"
      identifier = "6217"

    [[inputs.opcua_listener.group.nodes]]
      name = "heater_on"
      identifier = "6212"

    [[inputs.opcua_listener.group.nodes]]
      name = "overheated"
      identifier = "6214"

[[processors.regex]]
  order = 1
  [[processors.regex.fields]]
    key = "Quality"
    pattern = '^.*\((0x[0-9A-Fa-f]+)\)$'
    replacement = "${1}"

[[processors.rename]]
  order = 2
  [[processors.rename.replace]]
    field = "Quality"
    dest = "quality"

[[outputs.arc]]
  url = "http://<writer-endpoint>:8000/api/v1/write/msgpack"
  api_key = "${ARC_TOKEN}"
  database = "plant_events"
  content_encoding = "gzip"
  • trigger is Status, StatusValue or StatusValueTimestamp. If you set a data_change_filter without trigger, it defaults to Status, which reports status changes only, not value changes. Set StatusValue explicitly.
  • deadband_type = "Absolute" reports a change only when the value moves by more than deadband_value. "Percent" needs the node to have an EURange property.
  • For nodes without monitoring_params, Telegraf requests a sampling_interval of 0 (the fastest rate the server supports) and leaves the data change filter to the server's default.
  • The server may reject a subscription_interval or sampling_interval it cannot meet; check the server's documentation.

Over the same five minutes against the same server, the polling config above wrote 300 rows per node, and this subscription wrote 101 for current_temperature, 4 for heater_on, 6 for overheated and none for the unchanged target_temperature. Each subscription row is a change, so state durations come from a window function:

WITH transitions AS (
  SELECT
    time,
    overheated,
    LEAD(time) OVER (ORDER BY time) AS next_change
  FROM plant_events.boiler
  WHERE asset = 'boiler-2'
    AND overheated IS NOT NULL
)
SELECT
  time                                          AS started,
  next_change                                   AS ended,
  EXTRACT(EPOCH FROM (next_change - time))      AS seconds
FROM transitions
WHERE overheated
ORDER BY started;

Remote sites

Where the link from the plant to the data center is unreliable, run Telegraf and an Arc instance at the site, next to the OPC UA server, and ship the Parquet files to the central cluster with edge sync. The site initiates every transfer, so nothing needs inbound access to the plant network.

Troubleshooting

SymptomCauseFix
no suitable endpoint foundNo server endpoint matches security_policy and security_modeMatch both to an endpoint the server publishes
Connects, then fails with a DNS or dial errorThe server advertises a hostname Telegraf cannot resolveFix the advertised hostname on the server, or make it resolvable
StatusBadNodeIDUnknownWrong identifier, or a namespace index that changedBrowse the server for the node; switch to namespace_uri
status not OK for node ... in the log, missing rows in ArcNon-Good status codes are droppedExpected; add codes to additional_valid_status_codes to keep them
namespace urls require a server NamespaceArrayopcua_listener with namespace_uri or nsu= node IDs on Telegraf before 1.39.0Upgrade Telegraf, or use numeric namespace indexes
arc returned status 401Empty or wrong ARC_TOKEN in Telegraf's environmentCheck the variable inside the running process or container
Duplicate rows with identical timestampsPolling with timestamp = "source"Use gather or server for polling

Next steps

  • Telegraf: the Arc output plugin in detail
  • Edge sync in clusters: ship data from remote sites to the central cluster
  • RBAC: scope collector tokens to the databases they write